1. |
If the Defogger SW is ON after the ALT "L"
is ON in the state that the IGN1 SW is ON, then the Defogger output
shall be ON for 20 minutes. (Operating in the state of the ENGINE
RUNNING) |
2. |
If the DEFOGGER SW is ON again while the
DEFOGGER output is ON, then the DEFOGGER output shall be
OFF. |
3. |
If the ALT "L" is OFF or IGN1 is OFF while
the DEFOGGER output is ON, then the DEFOGGER output shall be
OFF. |
4. |
If the ALT "L" > 10 volts, then it shall
be in the Engine Running State (ALT "L" shall be ON); if the ALT "L"
< 5 volts, then it shall be in the Engine Stop State (ALT "L"
shall be OFF). Also, if the ALT "L" is more than 5 and less than 10
volts, then the former state shall be
maintained. |
5. |
If the defogger SW is pressed and the ALT
"L" is ON, there shall be no the DEFOGGER relay output.

T1 : 60 ± 20 msec, T2 : 20 ± 1
min. | |